Critical CVSS 9.8 Security news
Danfoss AK-SM 8xxA (CVE-2026-129713): critical flaw in refrigeration controllers, no patch yet
On 24 November 2026 CISA published an advisory on a critical vulnerability in Danfoss AK-SM 8xxA refrigeration controllers, which supermarkets and warehouses use to manage refrigerated cases and cold rooms. The stack overflow needs no authentication and, according to CISA, could lead to code execution. No fixed version has been released. These are the same kind of devices that attackers have been hitting across Europe since October.
Key points
- On 24 Nov 2026 CISA published advisory ICSA-26-328-03 on CVE-2026-129713 in Danfoss AK-SM 8xxA refrigeration controllers, version 5.4.0 and earlier.
- It is a stack-based buffer overflow in an unauthenticated CGI handler. A crafted POST request can restart the web server and, according to CISA, could potentially run code with its privileges. CVSS 3.1 is 9.8, CVSS 4.0 is 9.3.
- There is no fix yet. Danfoss plans one in version 5.5.x and intends to remove the option to disable Strict Mode in later releases.
- The flaw was reported by Carlo Meijer of Midnight Blue. CISA knows of no exploitation, but Danfoss AK-SM controllers have been among the targets of the wave of attacks on refrigeration in Europe since October.
Vulnerabilities: CVE-2026-129713
What happened
On 24 November 2026 CISA published advisory ICSA-26-328-03 on a critical vulnerability, CVE-2026-129713, in Danfoss AK-SM 8xxA (AK-SM 800A series) refrigeration controllers. Supermarkets, warehouses and other sites use these controllers to monitor and adjust refrigerated cases and cold rooms remotely. The CVE record went live in NVD on 20 November.
The flaw needs no authentication and there is no fixed version yet. According to CISA, Danfoss plans to address it in an upcoming 5.5.x software release. It was reported by Carlo Meijer of Dutch firm Midnight Blue.
Technical details
According to CISA and NVD, it is a stack-based buffer overflow (CWE-121) in a CGI handler of the web interface that does not require a login. A network attacker sends a crafted HTTP/HTTPS POST request, corrupts memory and restarts the web server. CISA says the bug could hypothetically also allow code execution with web server privileges. Scores: CVSS 3.1 9.8 (CISA) and CVSS 4.0 9.3 (NVD, supplied by the CVE assigner).
In November Midnight Blue described six unpatched pre-authentication stack overflows in AK-SM800A versions up to 5.3.2, plus a separate bug that works even in Strict Mode, with CVEs listed as pending. The sources don't say whether CVE-2026-129713 is one of them.
Who is affected
Anyone running Danfoss AK-SM 8xxA version 5.4.0 or earlier (per CISA). Controllers whose web interface is reachable from the internet are most at risk; Midnight Blue counted hundreds of exposed Danfoss systems as of 10 November 2026.
Danfoss AK-SM controllers have been among the targets of the wave of attacks on refrigeration systems in Europe that France's CERT-FR has tracked since October, with reported defrost sabotage and spoiled stock. For background on the French investigation, see France blames Iranian units for refrigeration sabotage.
How to tell if you were compromised
Neither CISA nor Danfoss has published indicators of compromise, and CISA knows of no exploitation of this flaw. What to check:
- internet exposure – try opening the interface from outside your network, for example from a phone on mobile data,
- firewall, VPN or reverse-proxy logs – POST requests to the controller's CGI scripts from unknown addresses,
- unexpected web interface restarts – the symptom of an attempt as described by CISA,
- configuration and refrigeration state – changed setpoints, defrost schedules, accounts.
Our IOC extractor pulls addresses out of logs, and the CVSS calculator breaks down the score. Both run entirely in your browser.
What to do
- Take the web interface off the internet and don't give the controller a public IP address. The bug needs no login, so a password won't stop it.
- Allow remote access only through a VPN you control, including for your service contractor and any 4G modems they installed.
- Enable Strict Mode and use strong, unique passwords for every account – the vendor's recommendation.
- Update as soon as version 5.5.x is released. Until then, steps 1–3 are your protection.
Timeline
- 11–12 Oct 2026 – a wave of attacks on refrigeration controllers in Europe begins; CERT-FR issues an alert.
- 5 Nov 2026 – the Czech cyber agency NÚKIB warns about the wave, naming Danfoss AK-SM.
- November 2026 – Midnight Blue discloses six unpatched AK-SM800A flaws (without technical details).
- 20 Nov 2026 – CVE-2026-129713 is published in NVD, referencing Danfoss advisory DSA-2026-12-01.
- 24 Nov 2026 – CISA publishes ICSA-26-328-03; no fix is available yet.
We verified the description, affected versions, scores, mitigations and fix status in CISA's machine-readable advisory (CSAF) and the NVD record. The Danfoss page and CISA's web version returned 403 errors for us, so the vendor's recommendations are given as quoted by CISA. Background on earlier flaws and attacks comes from Midnight Blue's blog.
Verified against sources on 25 November 2026.
FAQ
Does enabling Strict Mode help?
Danfoss recommends it, and Midnight Blue says Strict Mode blocks unauthenticated access to most of the web interface. But Midnight Blue also described a different bug that works even with Strict Mode on. Treat it as an extra layer, not a substitute for taking the device off the internet.
Is this one of the six flaws Midnight Blue wrote about?
Public sources don't say. In November Midnight Blue described six unpatched pre-authentication stack overflows in versions up to 5.3.2, with CVEs pending. CVE-2026-129713 was reported by a researcher from the same company, but neither CISA nor NVD maps it to a specific bug from that post.
Is anyone exploiting it?
CISA reported no known public exploitation as of 24 November. Earlier, publicly known flaws in Danfoss and Copeland controllers were exploited in the autumn attack wave, so assume exposed devices will be probed.
Sources